    1. Product overview and application scope
      KYN28-12 metal-enclosed switchgear (hereinafter referred to as switchgear) is a new type of product designed and developed by the company on the basis of absorbing advanced manufacturing technology at home and abroad, which can replace a variety of old type metal-enclosed switchgear, such as KYN1-10, JYN2-10, GBC-10 and other products. Its products have the following obvious advantages:
      1.1 The shell of the product is completely assembled by bolts after multiple bending and forming of the aluminum-clad steel plate processed by CNC machine tool, which has high mechanical strength and effectively ensures the neat and beautiful appearance of the product. The cabinet door is sprayed with plastic coating, which has strong impact resistance and corrosion resistance. The product housing has IP4X level of protection.
      1.2 The main switch of this product can be configured with VY4, VD4 series vacuum circuit breaker, C3 series fixed load switch, and can also be configured with a variety of domestic series vacuum circuit breaker (such as VS1, VH1, VK, ZN28) to replace similar foreign products.
      1.3 No matter what type of circuit breaker is selected, the bare conductor air insulation distance must be greater than 125mm, and the composite insulation must be greater than 60mm. The circuit breakers have the unique advantages of long life, high parameters, less maintenance and small size.
      KYN28-12 armoury medium metal enclosed switchgear is suitable for 3.6-12KV three-phase AC 50Hz power grid to receive and distribute electrical energy, and to control, monitor and protect the circuit. Can be used in single bus, single bus segment system or double bus system. Switchgear conforms to IEC298 “Rated voltage above 1KV 52KV and below AC metal enclosed switchgear and control equipment”, IEC694 “High voltage switchgear and control equipment Regulations”, China GB3906 “3-35KV AC metal enclosed switchgear” and DL404 “Indoor AC high voltage switchgear ordering conditions”, German DIN.VDE670 “AC switchgear with rated voltage above 1KV” and other standards. And it has perfect and reliable anti-misoperation function.
    2. Model meaning
    1. Normal operating conditions
      3.1 Ambient air temperature: upper limit +40℃, lower limit -10℃;
      3.2 Relative humidity: the daily average is not more than 95%; The monthly average is not more than 90%;
      3.3 Altitude: no more than 1000m;
      3.4 Earthquake intensity does not exceed 8 degrees;
      3.5 No fire, explosion danger, serious pollution, chemical corrosion and violent vibration occasions, when the use of conditions beyond the above scope, should be negotiated by the user and our company to determine the scope and technical measures.
    2. Technical parameters
      4.1 Technical Specifications of the switchgear
    entrySingle positionparameter
    Rated voltagekV3.6、7.2、12
    Rated frequencyHz50
    Circuit breaker rated currentA630、1250、1600、2000、2500、3150
    Rated current of switchgearA630、1250、1600、2000、2500、3150
    Rated dynamic stability current (4s)kA16、20、25、31.5、40、50
    Rated dynamic stable current (peak)kA40、50、63、8、100、125
    Rated short-circuit breaking currentkA16、20、25、31.5、40、50
    Rated short-circuit switch closing current (peak)kA40、50、63、80、100、125
    Rated insulation level1m?in power frequency withstand voltagekV243242
    Lightning impulse, withstand voltagekV406075
    Class of protectionThe enclosure is IP4X, and the compartment and circuit breaker room doors are IP2X when opened
    Basic form of the dimensions of the switchgear (see Figure 1, Figure 2)
    5.1 The construction of the installation foundation of the switch cabinet shall comply with the relevant provisions of the “Technical Specification for Electric Power Construction and Acceptance”.
    5.2 The installation foundation of the switch cabinet is generally divided into two pours of concrete. The first installation of components for the switch cabinet is the installation foundation of Angle steel or square steel and channel steel components. The second pouring concrete is the supplementary layer of the ground, the general thickness is 60mm, and the concrete height should be 1-3mm lower than the component plane when pouring the supplementary layer of concrete.

    A busbar compartment
    B circuit breaker compartment
    C cable compartment
    D instrument compartment
    Shell
    1.1 pressure release plate
    1.2 control cable cover
    2. branch busbar
    3. busbar
    4. static contact device
    5. spring contact
    6. grounding knife
    7. current transformer

    8. voltage transformer
    9. removable partition
    10. secondary plug
    11. auxiliary switch
    12. movable curtain plate
    13. removable trolley
    14. grounding knife operating mechanism
    15. cable sealing terminal
    16. bottom plate
    17. screw mechanism
    18. grounding main busbar
    19. removable horizontal partition

    KYN28-12 switch cabinet basic structure diagram

    Figure 1 Dimensions of the switchgear

    Figure 2 Basic form

    發(fā)表回復(fù)

    您的郵箱地址不會被公開。 必填項(xiàng)已用 * 標(biāo)注

    国产精品乱码一区二区三区 | 亚洲AV成人无码久久精品老人| 亚洲国产精品嫩草影院| 精品久久久久久中文字幕| 日本精品视频一区二区三区| 久久久久久九九99精品| 久久亚洲精品无码网站| 国产精品手机在线观看你懂的| 精品国偷自产在线| 亚洲国产精品国自产拍AV| 国产精品伦理久久久久久| 人人妻人人澡人人爽人人精品浪潮| 久久久久久久国产精品电影| 国产精品无打码在线播放| 在线观看麻豆精品国产不卡| 91精品国产色综久久| 精品999久久久久久中文字幕| 一本精品99久久精品77| 久久亚洲精品11p| 亚洲精品福利你懂| 少妇人妻偷人精品免费视频| 国产精品极品美女免费观看| 在线精品一卡乱码免费| 熟妇人妻VA精品中文字幕| 97久久精品午夜一区二区| 亚洲精品无码久久久久牙蜜区| 久久香蕉超碰97国产精品| 少妇人妻偷人精品一区二区| 国产69精品久久久久99尤物| 久久国产亚洲精品| 69精品免费视频| 久久精品国产第一区二区| 少妇亚洲免费精品| 久久久久久精品无码人妻| 日韩精品无码免费一区二区三区| 四虎影视永久在线观看精品| 91麻豆精品国产| 精品一久久香蕉国产线看播放 | 亚洲福利精品电影在线观看| 精品久久久久久中文字幕无碍| 亚洲色偷精品一区二区三区|